95 Proposed called BlkStatCreated: 16 Mar 2005 Status: In Force (green) Part: Part 7-4 (2003) Links: Page: Clause: 5.3.4 Paragraph: Category: Issue for edition 2 of this part Issue In relation with the previous comment, when the local device is located in other building than the HMI is, and an operaton is in front the device and want to lock the control from the HMI (because he has change from remote telecontrol to local control) a new extended attribute “proposed called BlkStat” SPS type at LN0 could be necessary.
Proposal Add a new attribute BlkStat SPS type at LN0. Other possibilitie is to locate it as extension, because it is not as important as the previous one.