Data Name PwrSupAlm:
Current definition “ PwrSupAlm Alarm from external power supply if PwrSupAlm is TRUE. May be an external contact. It refers always to the local power supply of the IED modelled by LPHD and not to the health (EEHealth) of the complete external supply system”
Comment: The text says "Alarm from external ..." But later it says: "not to the health (EEHealth) of the ... external supply"
The Alm represents alarms of the physical device in which the LD is implemented. Not the EXTERNAL!!
Proposal
Remove "external" at the beginning of the sentence to read:
"Alarm from power supply ..."
Discussion
Created
Status
15 Jul 05
In Force (green)
Text in 7-4 should be replaced by:
PwrSupAlm Alarm from power supply allocated to the Physical Device if PwrSupAlm is TRUE.
02 Apr 05
Ballot Period
Proposal: accept the comment with some explantation what is internal and external in this case. Depending in the power supply design, PwrSupAlm may be external or internal.