73 Instances of LN SIMG (SIML)Created: 15 Mar 2005 Status: In Force (green) Part: Part 7-4 (2003) Links: Page: Clause: 5.11.3, 5.11.4 Paragraph: Category: Issue for edition 2 of this part Issue It is stated that additional measuring points shall be added by numbered extension of the data. That approach is not practicable because it results in a complete multiplication of all data (another measuring point is a different sensor with different name plate and health, etc.). Proposal Modify text and request to use a different instance of the LN SIMG (SIML)