588 GAPC for modelling generic automation functionsCreated: 19 Dec 2007 Status: In Force (green) Part: Part 7-4 (2003) Links: Page: 44 Clause: 5.7.1 Paragraph: Category: Issue for edition 2 of this part Issue GAPC should be used to model in a generic way automation function not covered by LNs A,C,M,P,R. But GAPC contains the mandatory objects Str (ACD) and Op (ACT) which cannot be used for non-protection-related automation functions. Proposal Set Str/Op to "Optional" (O).