502 Get/SetDataValue(s) with multiple referencesCreated: 13 Apr 2007 Status: In Force (green) Part: Part 7-2 (2003) Links: Page: 53 Clause: 10.4.1 Paragraph: Figure 14 Category: Issue for edition 2 of this part Issue In the figure 14 the services GetDataValue/SetDataValue seem to hold more than one reference in the request.
Proposal Modify the Figure 14 to describe clearly that only one reference is sent in each service ACSI-Get/SetDataValue-Request.