347 Same member notification in BRCBCreated: 21 Jul 2006 Status: Not Applicable Part: Part 7-2 (2003) Links: Page: 078 Clause: 14.2.2 Paragraph: 14.2.2.9 Category: No impact on this part Issue The first sentence in the third paragraph reads "In the case where a second internal notification of the same member of a DATA-SET has occured prior to the expiration of BufTm, the BRCB shall for status information behave as if BufTm has expired and immediately send the report, restart the timer with BufTm and process the second condition; or ...".
Proposal Allowing "buffered" status events from the same member in DATA-SET within BufTm avoids sending a report for each change of the member, especially if the change rate is fast.