The conceptual specification indicates:
"The sample rate (data attribute smpRate of a configurable data) determines how often the value shall be sampled."
1) SAV CDC does not contain a data attribute smpRate
2) The Txxx.SmpRte data object indicates how often the value has beeen sampled.
3) the MV/CMV.smpRate attribute inidcates how often the sample has been observed for actualizing the inst component.
Proposal
Modify the clause 6.4.3.1 to indicate that:
The Txxx.SmpRte data object indicates how often the value has beeen sampled.
see tissue #1840
Discussion
Created
Status
Approved Editorial
12 Dec 23
Editorial
Editorial change:
Modify the clause 6.4.3.1:
Replace:
The sample rate (data attribute smpRate of a configurable data) determines how often the value shall be sampled.
With:
The Txxx.SmpRte data object indicates how often the value has been sampled.
22 Aug 23
Approval (Editoral)
This is not a change in CDC, many settings are not writable.
This is an editorial change, following the linked tissue.
22 Aug 23
Approval (Editoral)
TPWG:
Is this a FC change?
SmpRte is ING - setting. Change to INS?
25 Jul 23
Discussion (red)
NO issues found, move to CTP
11 Jul 23
Conformance Test Preparation
No objection, proceed to next state.
09 Jun 23
Analysis Of Compatibility
Modify the clause 6.4.3.1:
Replace:
The sample rate (data attribute smpRate of a configurable data) determines how often the value shall be sampled.
With:
The Txxx.SmpRte data object indicates how often the value has been sampled.