1444 Need to support fixed and SCT controlled DatasetsCreated: 06 Oct 2015 Status: In Force (green) Part: Part 6 (2009-12; Edition 2) Page: 63 Clause: Paragraph: Table 11 and others Category: Issue may impact interoperability of implementations of Edition 2 Issue In the service section, an IED can declare “modify dataset” to be FALSE. That means, datasets in the IED cannot be changed by the system tool.
Proposal According to the discussion in the WG10 Meeting in Brussels, an attribute shall be added to the DatSet definition, in SCL, indicating if the datSet can be modified/deleted by an SCT. The new attribute will be defined as optional with a default value that is backward compatible with the current ED.2.